Customization: | Available |
---|---|
Task: | Program |
Structure: | Combination |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | SM 1231 AI 4x13 bits |
Order number | UN 231-4HD32-0XB0 |
General | |
Dimension W x H x D ( mm ) | 45×100×75 |
Weight | 180 g |
Power consumption | 2.2 W |
Current consumption (SM bus) | 80 mA |
Current consumption (24 VDC) | 45 mA |
Analog input | |
Number of input channels | 4 |
Type | Voltage or current (differential): can be selected as a set of 2 |
Range | ±10 V,± 5 V,± 2.5 V, 0 - 20 mA or 4 - 20 mA |
Full-scale range (data word) | -27648 - 27648,Voltage;0-27648,current |
Overshoot/undershoot range (data word) |
Voltage:32,511 - 27,649/-27,649 - -32,512 Current:32,511 - 27,649/0 - -4,864 |
Overflow/underflow range (data word) |
Voltage:32,767 - 32,512/-32,513 - -32,768 Current0 - 20 mA:32,767 - 32,512/-4,865 - -32,768 Current4 - 20 mA:32,767 - 32,512/value less than -4,864 indicates an open circuit |
Accuracy | 12 bits + sign bit |
Maximum voltage/current | 35 V/±40 mA |
Smooth | None, weak, medium or strong |
Noise suppression | 400,60,50 or 10 Hz |
Isolation Field side and logic side Logic side with 24 V DC Field side with 24 V DC Passages and passages |
No |
Impedance | ≥ 9 MΩ(Voltage)/ ≥ 270 Ω,< 290 Ω(current) |
Accuracy( 25ºC/0 -55 ºC) | ±0.1 %/±0.2 % of full scale |
Common mode rejection | 40 dB,DC - 60 Hz |
Working signal rang | Signal plus common mode voltage must be less than +12 V and greater than -12 V |
Cable length (meter) | 100 meters, shielded twisted pair |
Diagnosis | |
Overflow/Underflow | √ |
Break circuit (Current) | 4 to 20 mA range only (if input below -4,864; 1.185 mA) |
Short circuit to ground (voltage) | not applicable |
24V DC low voltage | √ |