Customization: | Available |
---|---|
Task: | Program |
Structure: | Combination |
Still deciding? Get samples of US$ 100/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model No. |
X2-32TD-E0 |
UXPLC-32_STD_R |
||
physical characteristics |
||||
Dimension(W*H*D) |
150*90*77cm |
|||
consumption |
12W |
12W |
||
Power characteristics |
||||
Rated voltage |
DC 24V |
AC 220V |
||
input voltage |
DC 20.4 to 28.8V |
AC 85 to 264 |
||
Input current |
150mA(only CPU,24VDC hour) |
60/30mA(CPU,120/240VAC hour) |
||
surge current |
12A,28.8V DC hour |
20A,264V AC hour |
||
Fuse |
2A 60V Slow melt |
2A 60V Slow melt |
||
Sensor voltage |
L+ -1V |
L+ -1V |
||
Current supply (maximum) |
300mA |
300mA |
||
Isolation (Field and Logic) |
Non Isolated |
Non Isolated |
||
Memory characteristics |
||||
Program Memory |
64K |
|||
Data Memory |
10K |
|||
External memory card |
Supporting TF Card (developing now) |
|||
Conventional characteristics |
||||
Total number of timers |
Total 512 PCS,260 PCS 1ms, 46 PCS 10ms, 206 PCS 100ms |
|||
Total number of counters |
256 (including high-speed counts) |
|||
timer interrupt |
3 1ms resolution (recommended for use over 10ms) |
|||
Counter interruption |
6 interrupt numbers (4-way high-speed input) |
|||
Edge interruption |
Six rising or six falling edges |
|||
Analog potentiometer |
Not support |
|||
Real time clock |
Support |
|||
Slot options |
Not support |
|||
Power failure maintenance |
Support |
|||
Serial Communication Function |
||||
Interface |
One RS-485 interface and one RS232 interface |
|||
Serial Port Baud Rate |
Supports 9600 bps, 19200 BPS and 1152 200 BPS (three communication ports, two serial ports plus one BD board, one BD board is not recommended for use at the same time) |
|||
Communication protocol |
FX Monitoring Download Protocol, RS2 Protocol (Remove the original RS), Modbus Master and Slave Station |
|||
Maximum length of each section of cable |
Isolated interruption relays: 19.2 Kbps up to 1200 meters, no isolation relay 50 meters |
|||
Digital Input Characteristics |
||||
Local Integrated Digital Input Points |
16-point fixed input |
|||
Input type |
PNP/NPN |
|||
Rated voltage |
24VDC,4mA |
|||
Maximum Permissible Continuous Voltage |
30V DC |
|||
Surge voltage |
35VDC,0.5 |
|||
Logic 1 [Minimum] |
15VDC 2.5mA |
|||
Logic 0 [Maximum] |
5VDC 1mA |
|||
Permissible Leakage Current [Maximum] |
1mA |
|||
isolation |
yes |
|||
Photoelectric isolation |
500VAC 1 min |
|||
Input Rate of High Speed Counter |
Single-phase 200KHz [3]; AB phase 100KHz [3], supporting 4-fold counting |
|||
Cable Length (Maximum) |
Standard input: 500 meters (shielding line), 300 meters (non-shielding line); High-speed counting input: 50 meters (shielding line) |
|||
Digital Output Characteristics |
||||
Integrated Digital Output Points |
16 Transistor Output (Leakage Type) |
16 Relay Output |
||
type of output |
Solid-state-MOSFET |
Dry contact |
||
Rated Voltage |
24VDC |
24VDC or 250VAC |
||
Voltage range |
20.4~28.8VDC |
5~30VDC 5~250VAC |
||
Surge Current (Maximum) |
8A,100ms |
5A 4s 10% Duty cycle |
||
Logic 1 [Minimum] |
20VDC(Maximum current) |
none |
||
Logic 1 [Minimum]) |
0.1VDC,10 KΩ load |
none |
||
Rated current per point (maximum) |
0.75A (Reuse Design 0.2A) |
2A |
||
Rated current per common end (maximum) |
6A |
10A |
||
Rated current per common end (maximum) |
10uA |
none |
||
Lamp load [maximum] |
5W |
30W DC/200W AC |
||
Inductive Embedded Voltage |
none |
none |
||
Turn on resistance [contact] |
0.3ΩTypical value(Maximum 0.6Ω) |
0.2Ω |
||
Pulse frequency [maximum] |
4 channel:200KHz(Y0,Y1,Y2,Y3) |
1Hz |
||
Mechanical Life Cycle |
- |
10000000(none load) |
||
Contact life |
- |
100000(rated load) |
||
Shield |
500 m (normal output) |
500 m (normal output) |
||
Non Shield |
150 m (normal output) |
150 m (normal output) |
||
Environmental parameters |
||||
Working environment temperature |
-10ºC~70ºC(Horizontal installation),-10ºC~40ºC(vertical installations) |
|||
Transportation environment temperature |
-20ºC~80ºC |
|||
Environmental relative humidity |
5~95%,without condensation (RH grade 2, IEC 61131-2) |
|||
IP |
IP20 |
|||
electromagnetic compatibility |
Noise suppression, in line with IEC 61000-6-2 |
|||
Mechanical Level (Vibration) |
IEC60068,Part2-6/10up58Hz |